48K
60K
37K
7K
30K
42K
36K
24K
18K
12K
9K
SEER30
SEER30
SEER19
SEER19
SEER18
SEER18
SEER17
SEER17
SEER16
SEER16
SEER23
SEER23
SEER24
SEER24
SEER25
SEER25
SEER22
SEER22
SEER20
SEER20
Text Link
Multi Zone
Text Link
Single Zone

Error Codes & FAQ

High Wall (C-Series)
Code Description Possible Cause(s)
E0 IDU overcurrent protection
E1 Room temperature sensor failure
  • Damage of the room temperature sensor on the indoor unit
  • Poor contact of the room temperature sensor on the indoor unit
  • Damage of wiring of the room temperature sensor on the indoor unit
  • Damage of the main PCB on the indoor unit
E2 Outdoor coil sensor failure
  • Damage of the defrosting temperature sensor on the outdoor unit
  • Poor contact of the defrosting temperature sensor on the outdoor unit
  • Damage of the wiring of the defrosting temperature sensor on the outdoor unit
  • Damage of the main PCB on the outdoor unit
E3 Indoor coil sensor failure
  • Damage of the temperature sensor on the indoor unit
  • Poor contact of the temperature sensor on the indoor unit
  • Damage of wiring of the temperature sensor on the indoor unit
  • Damage of the main PCB on the indoor unit
E4 PG motor or DC fan failure
  • Low voltage
  • Poor wiring
  • Damage of the main PCB on the indoor unit
  • Damage of the motor
E5 Internal and external communication failure
  • Damage of the main PCB on the indoor unit
  • Damage of the main PCB on the outdoor unit
  • Poor wiring
F0 Outdoor fan failure
  • Damage of motor
F1 Module protection failure
  • Compressor damage
  • Compressor IPM module damage
  • System blockage
F2 PFC protection failure
  • Damage of the PFC circuit components
  • Reactor damage
F3 Compressor startup failure or out-of-step operation
  • Compressor power line not connected
  • Compressor sequence connection error
  • Damage of compressor
  • System blockage
F4 Outdoor exhaust sensor failure
  • Damage of the discharge temperature sensor on the outdoor unit
  • Poor contact of the discharge temperature sensor on the outdoor unit
  • Damage of the wiring of the discharge temperature sensor on the outdoor unit
  • Damage of the main PCB on the outdoor unit
F5 Compressor top cover protector failure
  • Damage of compressor top cover switch
  • System blockage
F6 Outdoor environmental temperature sensor failure
  • Lack of refrigerant
  • Heat exchange viscera
F7 Over & under voltage safeguard
  • Excessive input voltage
  • Lower input voltage
F8 Outdoor main control board & communicating module failure
  • Damage of the driver PCB on the outdoor unit
  • Damage of the main PCB on the outdoor unit
  • Poor wiring
F9 Outdoor E-side failure
  • Fault with the EE chip on the outdoor PCB
L0 DC over voltage and under voltage failure
  • Excessive input voltage
  • Lower input voltage
L1 Compressor phase current over current protection
  • Damage of compressor
  • System viscera
L2 Compressor out-of-step failure
  • Damage of compressor
  • System viscera
L3 Compressor phase loss failure
  • Damage of compressor
  • Compressor power line not connected
L4 Compressor driver module IPM failure
  • Compressor drive module damage
L5 PFC over-current hardware protection
  • Damage of the PFC circuit components
  • Reactor damage
L6 PFC over-current software protection
  • Excessive running current of the unit
  • Voltage drops abruptly during operation
L7 Current detection AD abnormal protection
  • Sensor damage of compressor IPM module
L8 IPM temperature sensor fault
  • Sampling resistance damage
  • Excessive operating power of compressor
L9 IPM temperature sensor fault
  • Compressor IPM module sensor damage
  • Poor contact between compressor IPM module and radiator
LA Compressor start-up failure
  • Compressor power line not connected
  • Compressor sequence connection error
  • Damage of compressor
LC PFC current detection AD abnormal protection
  • Damage of the PFC circuit components
  • Reactor damage
LD DC fan current sense AD abnormal protection
  • Sensor damage of DC fan module
LE DC fan phase loss protection
  • Damage of DC fan motor
  • DC fan power line not connected
LF DC fan out-of-step protection
  • Damage of DC fan motor
LH DC fan IPM protection
  • IPM device of DC motor is faulty
P3 Liquid deficiency problem
  • Lack of refrigerant
  • Stop valve unopened
No matching error codes found.
High Wall (LC)
Code Description Possible Cause(s)
Cooling indicator flashes 2 PFC protection fault / 120N discharge high-temperature protection
  • PFC protection fault
  • 120N discharge high-temperature protection
Cooling indicator flashes 4 Cooling overload protection fault lock
  • Cooling overload protection fault lock
Cooling indicator flashes 5 Discharge temperature protection fault lock
  • Discharge temperature protection fault lock
Cooling indicator flashes 6 Indoor heating over-temperature protection lock
  • Indoor heating over-temperature protection lock
Cooling indicator flashes 7 Indoor anti-freeze protection
  • Indoor anti-freeze protection
Cooling indicator flashes 8 Outdoor unit overcurrent protection lock / Indoor unit overcurrent
  • Outdoor unit overcurrent protection lock
  • Indoor unit overcurrent
Heating indicator flashes 1 Indoor ambient sensor fault
  • Indoor ambient sensor fault
Heating indicator flashes 3 Indoor coil sensor fault
  • Indoor coil sensor fault
Heating indicator flashes 4 Indoor motor circuit fault
  • Indoor motor circuit fault
Heating indicator flashes 5 Indoor-outdoor communication fault
  • Indoor-outdoor communication fault
Heating indicator flashes 6 Low-pressure switch protection or Low refrigerant protection
  • Low-pressure switch protection
  • Low refrigerant protection
Timer indicator flashes 1 Outdoor unit overcurrent protection lock / Indoor unit overcurrent
  • Outdoor unit overcurrent protection lock
  • Indoor unit overcurrent
  • IPM over-temperature protection
  • 120AP phase loss/reverse phase protection
Timer indicator flashes 2 Outdoor coil sensor fault
  • Outdoor coil sensor fault
Timer indicator flashes 3 Compressor start failure or out-of-step fault
  • Compressor start failure or out-of-step fault
Timer indicator flashes 4 Compressor discharge sensor fault
  • Compressor discharge sensor fault
Timer indicator flashes 5 Compressor housing sensor fault
  • Compressor housing sensor fault
  • Compressor housing temperature protection
  • High-pressure switch protection/fault
Timer indicator flashes 6 Outdoor ambient sensor fault
  • Outdoor ambient sensor fault
Timer indicator flashes 7 Over/under voltage protection
  • Over/under voltage protection
Timer indicator flashes 8 Outdoor unit communication fault
  • Outdoor unit communication fault
  • Compressor over-power protection
Timer indicator flashes 9 Outdoor EE fault
  • Outdoor EE fault
Timer indicator flashes 10 Suction sensor fault
  • Suction sensor fault
Timer indicator flashes 11 Outdoor fan motor fault
  • Outdoor fan motor fault
No matching error codes found.
Multi-Zone (High Wall Unit)
Code Description Possible Cause(s)
E1 Fault with the room temperature sensor on the N# indoor unit
  • Damage of the room temperature sensor on the indoor unit
  • Poor contact of the room temperature sensor on the indoor unit
  • Damage of wiring of the room temperature sensor on the indoor unit
  • Damage of the main PCB on the indoor unit
E2 Fault with the defrosting condenser temperature sensor on the outdoor unit
  • Damage of the defrosting temperature sensor on the outdoor unit
  • Poor contact of the defrosting temperature sensor on the outdoor unit
  • Damage of the wiring of the defrosting temperature sensor on the outdoor unit
  • Damage of the main PCB on the outdoor unit
E3 Fault with the temperature sensor in the middle of N# indoor evaporator
  • Damage of the temperature sensor on the indoor unit
  • Poor contact of the temperature sensor on the indoor unit
  • Damage of wiring of the temperature sensor on the indoor unit
  • Damage of the main PCB on the indoor unit
E4 Fault with the fan motor of N# indoor unit
  • Low voltage
  • Poor wiring
  • Damage of the main PCB on the indoor unit
  • Damage of the motor
E5 Communication error between the outdoor unit and the N# indoor unit
  • Damage of the main PCB on the indoor unit
  • Damage of the main PCB on the outdoor unit
  • Poor wiring
E8 Communication error between the display board and main PCB of the indoor unit
  • Damage of the main PCB on the indoor unit
  • Damage of the display board on the indoor unit
  • Poor wiring
F0 Fault with the fan motor of outdoor unit
  • Damage of motor
F1 Module protection failure
  • Compressor damage
  • Compressor IPM module damage
  • System blockage
F2 Compressor drive PFC protection
  • Damage of the PFC circuit components
  • Reactor damage
F3 Compressor protection failure
  • Compressor power line not connected
  • Compressor sequence connection error
  • Damage of compressor
  • System blockage
F4 Fault with the discharge temperature sensor
  • Damage of the discharge temperature sensor on the outdoor unit
  • Poor contact of the discharge temperature sensor on the outdoor unit
  • Damage of the wiring of the discharge temperature sensor on the outdoor unit
  • Damage of the main PCB on the outdoor unit
F5 Temperature protection of compressor top cover
  • Damage of compressor top cover switch
  • System blockage
F6 Fault with the environmental temperature sensor on the outdoor unit
  • Damage of the environmental temperature sensor on the outdoor unit
  • Poor contact of the environmental temperature sensor on the outdoor unit
  • Damage of the wiring of the environmental temperature sensor on the outdoor unit
  • Damage of the main PCB on the outdoor unit
F7 Fault with the over-voltage or low-voltage protection
  • Excessive input voltage
  • Lower input voltage
F8 Communication error between the driver PCB and main PCB of the outdoor unit
  • Damage of the driver PCB on the outdoor unit
  • Damage of the main PCB on the outdoor unit
  • Poor wiring
F9 Fault with the outdoor unit EEPROM
  • Fault with the EE chip on the outdoor PCB
FA Fault with the suction temperature sensor
  • Damage of the suction temperature sensor on the outdoor unit
  • Poor contact of the suction temperature sensor on the outdoor unit
  • Damage of the wiring of the suction temperature sensor on the outdoor unit
  • Damage of the main PCB on the outdoor unit
H1 Fault with the drainage on N# indoor unit
  • Float switch disconnected or poor wiring
  • Error setting of model parameters
  • Drain plug
  • Damage of the pump
H2 Communication error between the wired controller and main PCB of the indoor unit
  • Damage of the main PCB on the indoor unit
  • Damage of the display board on the indoor unit
  • Poor wiring
H3 Fault with the liquid line thermistor on the N# indoor unit
  • Damaged liquid line thermistor
  • Poor contact
  • Damaged wiring
  • Damaged main PCB on indoor unit
H4 Fault with the gas line thermistor on the N# indoor unit
  • Damaged gas line thermistor
  • Poor contact
  • Damaged wiring
  • Damaged main PCB on indoor unit
H5 Protection low temperature discharge
  • Temperature sensor shedding
  • Damage of the main PCB on the outdoor unit
H6 Low pressure switch protection
  • Lack of refrigerant
  • Stop valve unopened
  • Damage of low pressure switch
H7 Low pressure protection
  • Lack of refrigerant
  • Heat exchange viscera
H8 Fault of four-way valve
  • Damage of four-way valve
  • Damage to coil of four-way valve
H9 Inter-computer communication line connection fault
  • Damaged or disconnected physical cable or plugs
HE Abnormal temperature sensor in IPM/PFC module
  • Driver board IPM/PFC module device is broken
HF Abnormal temperature sensor in IPM/PFC module
  • Driver board IPM/PFC module device is broken
J8 Over-current protection of the compressor drive modular
  • Excessive running current of the unit
  • Voltage drops abruptly during operation
L0 Overvoltage and undervoltage protection of indoor DC motor / Over-voltage protection of the compressor drive modular
  • Excessive input voltage
  • Lower input voltage
L1 Overvoltage protection of compressor
  • Damage of compressor
  • System viscera
L2 Compressor operation failure
  • Damage of compressor
  • System viscera
L3 Phase-absence protection of compressor
  • Damage of compressor
  • Compressor power line not connected
L4 IPM fault of compressor drive module
  • Compressor drive module damage
L5 Compressor drive PFC hardware protection
  • Damage of the PFC circuit components
  • Reactor damage
L6 Compressor drive PFC software protection
  • Excessive running current of the unit
  • Voltage drops abruptly during operation
L7 AD abnormal protection for compressor current detection
  • Sensor damage of compressor IPM module
L8 Compressor superpower protection
  • Sampling resistance damage
  • Excessive operating power of compressor
L9 IPM temperature sensor fault
  • Compressor IPM module sensor damage
  • Poor contact between compressor IPM module and radiator
LA Compressor failed to start
  • Compressor power line not connected
  • Compressor sequence connection error
  • Damage of compressor
LC Compressor drive PFC (Power Factor Correction) protection
  • Damage of PFC circuit components
  • Reactor damaged
LD Fault with the fan motor of outdoor unit
  • Damage of motor
LE Fault with the fan motor of outdoor unit
  • Damage of motor
LF Fault with the fan motor of outdoor unit
  • Damage of motor
LH IPM protection of outdoor DC fan drive modular
  • The IPM device of DC motor is faulty
P2 High pressure switch protection
  • System dirty blocking
  • Damage of high voltage pressure switch
P3 Low refrigerant
  • Lack of refrigerant
  • Stop valve unopened
P4 Cooling high temperature protection of outdoor unit / Heating high temperature protection of indoor unit
  • Poor condenser heat exchange
  • Poor evaporator heat exchange
P5 High discharge temperature protection
  • Lack of refrigerant
  • Stop valve unopened
  • Damaged main PCB on outdoor unit
P6 Cooling high temperature protection of outdoor unit / Heating high temperature protection of indoor unit
  • Poor condenser heat exchange
  • Poor evaporator heat exchange
P7 Indoor anti-freezing protection
  • Clogged air filter
  • Dust on indoor heat exchanger
  • Defective thermistor
  • Defective PCB
  • Indoor fan defective
P8 Over-current protection of the compressor drive modular
  • Excessive running current of the unit
  • Voltage drops abruptly during operation
No matching error codes found.
Multi-Zone (Cassette, Floor & Ceiling, Slim Duct)
Code Description Possible Cause(s)
31 Module protection failure
  • Compressor damage
  • Compressor IPM module damage
  • System blockage
32 Fault with the driver EEPROM
  • Damage of the EE chip of driver board
34 Compressor protection failure
  • Compressor power line not connected
  • Compressor sequence connection error
  • Damage of compressor
  • System blockage
35 AC over-current protection of the whole machine
  • Excessive running current of the unit
  • Voltage drops abruptly during operation
36 Fault with the over-voltage or low-voltage protection
  • Excessive input voltage
  • Lower input voltage
39 IPM temperature sensor fault
  • Compressor IPM module sensor damage
  • Poor contact between compressor IPM module and radiator
3C Outdoor DC fan motor over-current protection
  • Current of the outdoor DC fan is too high
3E Compressor drive PFC software protection
  • Damage of the PFC circuit components
  • Reactor damage
3F Compressor drive PFC hardware protection
  • Damage of the PFC circuit components
  • Reactor damage
3H Fault with the fan motor over-current protection
  • Damage of motor
3J Overvoltage protection of outdoor DC fan motor
  • Voltage of the outdoor DC fan is too high or too low
41 IPM protection of outdoor DC fan
  • IPM device of DC motor is faulty
A1 Fault with the room temperature sensor on the N# indoor unit
  • Damage of the room temperature sensor on the indoor unit
  • Poor contact of the room temperature sensor on the indoor unit
  • Damage of wiring of the room temperature sensor on the indoor unit
  • Damage of the main PCB on the indoor unit
A2 Fault with the temperature sensor in the middle of N# indoor evaporator
  • Damage of the temperature sensor on the indoor unit
  • Poor contact of the temperature sensor on the indoor unit
  • Damage of wiring of the temperature sensor on the indoor unit
  • Damage of the main PCB on the indoor unit
A3 Fault of temperature sensor at N# evaporator inlet
  • Damage of the temperature sensor at N# evaporator inlet
  • Poor contact of the room temperature sensor at N# evaporator inlet
  • Damage of wiring of the room temperature sensor at N# evaporator inlet
  • Damage of the main PCB on the outdoor unit
A4 Fault of temperature sensor at N# evaporator outlet
  • Damage of the temperature sensor at N# evaporator outlet
  • Poor contact of the room temperature sensor at N# evaporator outlet
  • Damage of wiring of the room temperature sensor at N# evaporator outlet
  • Damage of the main PCB on the outdoor unit
A5 Fault with the drainage on N# indoor unit
  • Float switch disconnected or poor wiring
  • Error setting of model parameters
  • Drain plug
  • Damage of the pump
A6 Fault with the fan motor on N# indoor unit
  • Low voltage
  • Poor wiring
  • Damage of the main PCB on the indoor unit
  • Damage of the motor
A9 Communication error between the outdoor unit and the N# indoor unit
  • Damage of the main PCB on the indoor unit
  • Damage of the main PCB on the outdoor unit
  • Poor wiring
AA Communication error between the wired controller and main PCB of the indoor unit
  • Damage of the main PCB on the indoor unit
  • Damage of the display board on the indoor unit
  • Poor wiring
AD Indoor anti-freezing protection
  • Blockage of heat exchanger in indoor refrigeration unit
  • Blockage of internal fan
C1 Fault with the environmental temperature sensor on the outdoor unit
  • Damage of the environmental temperature sensor on the outdoor unit
  • Poor contact of the environmental temperature sensor on the outdoor unit
  • Damage of the wiring of the environmental temperature sensor on the outdoor unit
  • Damage of the main PCB on the outdoor unit
C2 Fault with the defrosting temperature sensor on the outdoor unit
  • Damage of the defrosting temperature sensor on the outdoor unit
  • Poor contact of the defrosting temperature sensor on the outdoor unit
  • Damage of the wiring of the defrosting temperature sensor on the outdoor unit
  • Damage of the main PCB on the outdoor unit
C3 Fault with the discharge temperature sensor
  • Damage of the discharge temperature sensor on the outdoor unit
  • Poor contact of the discharge temperature sensor on the outdoor unit
  • Damage of the wiring of the discharge temperature sensor on the outdoor unit
  • Damage of the main PCB on the outdoor unit
C6 Fault with the suction temperature sensor
  • Damage of the suction temperature sensor on the outdoor unit
  • Poor contact of the suction temperature sensor on the outdoor unit
  • Damage of the wiring of the suction temperature sensor on the outdoor unit
  • Damage of the main PCB on the outdoor unit
C8 Fault with the temperature sensor in the middle of outdoor condenser
  • Damage of the temperature sensor on the outdoor unit
  • Poor contact of the temperature sensor on the outdoor unit
  • Damage of the wiring of the temperature sensor on the outdoor unit
  • Damage of the main PCB on the outdoor unit
E1 Fault of four-way valve
  • Damage of four-way valve
  • Damage to coil of four-way valve
E3 Protection high temperature discharge
  • Lack of refrigerant
  • Stop valve unopened
  • Damage of the main PCB on the outdoor unit
E8 High temperature protection for refrigeration outdoor
  • Poor outdoor heat transfer
F6 Low pressure protection
  • Lack of refrigerant
  • Heat exchange viscera
FH Protection low temperature discharge
  • Temperature sensor shedding
  • Damage of the main PCB on the outdoor unit
H1 High pressure switch protection
  • System blockage
  • Damage of high pressure switch
H4 Low pressure switch protection
  • Lack of refrigerant
  • Stop valve unopened
  • Damage of low pressure switch
J3 Communication error between the driver PCB and main PCB of the outdoor unit
  • Damage of the driver PCB on the outdoor unit
  • Damage of the main PCB on the outdoor unit
  • Poor wiring
J7 Fault with the outdoor unit EEPROM
  • Fault with the EE chip on the outdoor PCB
No matching error codes found.
Inverter Ducted System IDU
Code Description Possible Cause(s)
Light stays on for 5 minutes Normal (485/24V signal not received)
Lights blink 1 time and stop for 8 seconds 485 Communication abnormal between the ODU and IDU
  • Communication wiring fault between ODU and IDU
Lights blink 2 times and stop for 8 seconds Fault with the wired controller communication
  • Wired controller communication fault
Lights blink 3 times and stop for 8 seconds Fault with the fan motor of IDU
  • Damage of IDU fan motor
Lights blink 4 times and stop for 8 seconds Fault with the refrigerant sensor
  • Damage of refrigerant sensor
Lights blink 5 times and stop for 8 seconds Refrigerant leakage protection
  • Refrigerant leakage
Lights blink 6 times and stop for 8 seconds Fault with the room temperature sensor on the IDU
  • Damage of room temperature sensor on IDU
Lights blink 7 times and stop for 8 seconds Fault with the temperature sensor in the Middle evaporator of IDU
  • Damage of middle evaporator temperature sensor
Lights blink 8 times and stop for 8 seconds IDU coil pipe inlet/outlet temperature sensor failure
  • Damage of coil pipe inlet/outlet temperature sensor
Lights blink 9 times and stop for 8 seconds Operation mode abnormal
  • Operation mode abnormal
Lights blink 10 times and stop for 8 seconds Fault with ODU
  • ODU fault
No light Normal (485/24V signal received)
No matching error codes found.
Inverter Ducted System ODU
Code Description Possible Cause(s)
Light blinks 2 times Communication failure between IDU and ODU
  • Communication wiring fault
Light blinks 4 times Compressor failed to start
  • Compressor power line not connected
  • Compressor sequence connection error
  • Damage of compressor
Light blinks 6 times Fault with fan motor of ODU - Fan 1
  • Damage of ODU fan motor 1
Light blinks 7 times Fault with fan motor of ODU
  • Damage of ODU fan motor
Light blinks 9 times Compressor discharge temperature too high protection
  • Compressor discharge temperature too high
Light blinks 10 times Fault with over load protection of IDU in cooling mode
  • IDU overload in cooling mode
Light blinks 13 times Fault with the over-electric current protection
  • Over-electric current
Light blinks 17 times Fault with the low voltage protection
  • Low voltage
Light blinks 18 times Fault with the Environmental temperature sensor (Tao) on the ODU
  • Damage of Tao sensor on ODU
Light blinks 19 times Fault with the temperature sensor (Tcm) on the ODU
  • Damage of Tcm sensor on ODU
Light blinks 20 times Fault with the discharge temperature sensor
  • Damage of discharge temperature sensor
Light blinks 21 times Protection of compressor driving module for excessive temperature
  • Compressor driving module excessive temperature
Light blinks 22 times Fault with anti-high temperature protection of IDU in heating mode
  • IDU anti-high temperature protection in heating mode
Light blinks 24 times Fault with fan motor of ODU - Fan 2
  • Damage of ODU fan motor 2
Light blinks 26 times Low pressure switch protection
  • Lack of refrigerant
  • Stop valve unopened
  • Damage of low pressure switch
Light blinks 28 times Fault with the suction temperature sensor
  • Damage of suction temperature sensor
Light blinks 29 times High pressure switch protection
  • System blockage
  • Damage of high pressure switch
Light blinks 30 times Fault of four-way valve
  • Damage of four-way valve
  • Damage to coil of four-way valve
Light blinks 31 times Fault with the defrosting temperature sensor on the outdoor unit or low-pressure switch fault
  • Damage of defrosting temperature sensor
  • Low-pressure switch fault
Light stays on for 5 minutes Normal, compressor shut down (IDU and ODU do not use 485 communication)
No light Normal compressor running
No matching error codes found.

Frequently Asked Questions

What is Voice Control/Hello Lisa?

"Hello Lisa" is a voice control feature that lets you turn on or control your AUX air conditioner by simply saying "Hello Lisa" followed by a command, like adjusting the temperature or mode. It works without needing a remote, app, or internet connection, making it super easy and convenient to use hands-free.

How do I enable or disable the Voice Control Function Mode (referred to as "Hello Lisa")
  1. Switch the air conditioner to Dehumidification Mode.
  2. Set the temperature to 60 degrees Fahrenheit (or 16 degrees Celsius, depending on your unit's default scale).
  3. Press the "-" (minus) button on the remote control eight times in succession.

This sequence will toggle the voice control feature on or off. If the process does not yield the expected result, consult your model's user manual or contact AUX customer support for verification.

How do I connect the Wi-Fi function?

To connect your AUX mini-split to Wi-Fi, please check the Wi-Fi setup manual included with your indoor unit. To connect your AUX mini-split to Wi-Fi:

  • Find the Wi-Fi setup manual with your indoor unit.
  • Download the "AC Freedom" app on your phone (iOS/Android).
  • Follow the app's setup wizard to connect to a 2.4GHz Wi-Fi network.
How can I switch from Celsius to Fahrenheit and back?

To switch the display temperature between Celsius and Fahrenheit on your AUX air conditioner, press and hold the "+" (plus) and "-" (minus) buttons on the remote control at the same time for 3 seconds. The display should toggle between Celsius and Fahrenheit. Repeat the process to switch back.

What's "SOFT" mode?

The "SOFT" mode on your AUX air conditioner runs the unit at a lower fan speed to create a quiet, gentle airflow. This mode ensures comfortable cooling with minimal noise, making it ideal for relaxing or sleeping.

What's the "I-FEEL" feature?

The "I-FEEL" feature on your AUX air conditioner uses a temperature sensor in the remote control to monitor the temperature at your location in the room. It adjusts the air conditioner's cooling or heating to maintain your desired comfort level based on where you are, rather than the unit's location.

How does "Self-Cleaning" work?

The "Self-cleaning" feature on your AUX air conditioner cleans the indoor and outdoor unit's coil in three steps:

  • Freezing: The unit cools to freeze moisture on the coil.
  • Melting: It heats up to melt the ice, washing away dirt.
  • Drying: The fan runs to dry the coil completely.

The process takes about 30 minutes, leaving your AC clean and ready to use. Activate it using the "Self-Clean" button on your remote. Check your user manual for model-specific instructions.

How often should I clean my filter?

You should clean your AUX air conditioner's filter every 4 to 6 weeks to keep it running efficiently. If you use the AC heavily or live in a dusty area, clean it more often, like every 2 to 3 weeks

Ready to Feel
the Comfort?

Contact Us
Smart Climate Solutions

Our team will guide you in selecting the right system, ensuring efficient, reliable cooling tailored for your unique environment.